DSC Alarm Systems PC Range - Serial Connection

The following DSC panels are supported

PC1616
PC1832
PC1864


DSC PC Range User Manual - 

DSC User Manual DSC User Manual (3007 KB)

Click here for Remote Manager and Upload / Download settings

Or click here to view in browser

Panel Programming

The WebWay is designed to emulate the DSC T-Link module. A WebWayOne cable will be needed for integration or a cable is adapted to suit as follows,

WebWay SPT

DSC

232 T

Pin 1

RTN

Pin 2

RTN

Pin 3

232 R

Pin 4



 SPT Connections

Serial Connectivity PC1616 / PC1832 / PC1864 Configuration

Engineer login and set-up: 

1. Press *8 
2. Keypad displays ‘Enter Your Installer Code’   >   Press 5555
3. Keypad displays ‘Enter Section’   >  Press 015
4. Keypad displays ‘Toggle Option’ followed by’ 8 ‘ 
(This may have some set to numbers. If 7 is displayed, press 7 to remove it from the display. This disables Telephone line monitoring).
5. Press #   >  Press 301
6. Keypad displays may display some numbers and letters followed by lots of F’s Replace with ‘DCAA’ followed by all F’s. This adds TLink to route calls to.
7. Press #   >  Press 302 and do the same as in 301 but fill all with F’s. This will clear all possible telephone numbers
8. Press 350   >  Keypad displays ‘Enter Data’
9. Press 04 then a moment later 04 again. This sets up alarms to be reported in SIA. 
10. Press 380   >  Keypad displays ‘Toggle Option’ followed by 8  this may have some numbers set. If 1 is not displayed, press 1 to add it to the display. This enables the system communicator.
11. Press #   > Press 381
12. Keypad displays ‘Toggle Option’ followed by 8 this may have some numbers set. If 3 is displayed, press 3 to remove it from the display. This disables Automatic SIA codes.
13. Press #   >  Press 382
14. Keypad displays ‘Toggle Option’ followed by 8 this may have some numbers set. If 5 are not displayed, press 5 to add it to the display. This enables TLink communications.
15. Press #  >  Press 401
16. Keypad displays ‘Toggle Option’ followed by 8 this may have some numbers set. If 1 is not displayed, press 1 to add it to the display. This enables UDL communications to the DLS application.
17. Press #