The following panels have been integrated to the WebWay signalling solution

GE Aritech 
-CD95 
-CD72

WebWayOne Guide - 

CD95 Guide CD95 Guide (495 KB)

CD95 User Manual -

CD95 User Manual CD95 User Manual (2227 KB)

Click here for Remote Manager and Upload / Download settings 

Integration is via MPI232 Serial Connection.

Panel Configuration

To access the MPI232 settings you will need to  connect your PC to the MPI232's DTE serial port.
Run up a hyperterminal application (such as putty) set at 9600, None, 8, 1. 

Set switch 3 on the MPI232 module to OFF.

Power up MPI232 module.

You will see the following:
MPI V2.23 programming main menu

1. Central station menu
2. Report options
3. Protocol options
0. Exit MPI programming

Make your choice: 

Select 3: Protocol options

1. Modem init string: AT&K0&DE1V1Q0S0=0S7=10
2. Modem dial string: ATD
3. Modem hangup string : ATH
4. Modem connect string :
5. CLID string 1: 00001
6. CLID string 2: 00002
7. Baudrate RS-232 port : 9600
8. Baudrate V31bis port : 9600
0. Back to main menu

+. Next page
-. Previous page

Make your choice: 

Select 5: CLID string 1 and set to '00001'

CLID string 1: 00001
Press Enter key

Select +

Protocol options menu
1. One account per call:        Yes
2. One event per block:      Yes
3. Three digit event numbers:    No
4. Text in SIA:  Yes
5. PA auto-restore:      No
6. Dual reporting:                          No
7. Auto dial:                                    No
8. PC calls:                                 Yes
9. Protocol:  V24

0. Back to main menu

+. Next page
-. Previous page

Make your choice: Select 2: One event per block

One event per block (Y/N):Select Y

Do the same for 4: Select 'Y' for Text in SIA
Do the same for 8: Select 'Y' for PC calls

 Select +

Protocol options menu

1. Wait for modem reply : 005
2. Wait for modem dial reply : 010
3. Wait for redial : 015
4. Max dial attempts/CS : 240
5. Max modem command attempts: 003
6. Event delay : 020
7. DCD timeout : 255

0. Back to main menu

+. Next page
-. Previous page

Make your choice: Do the same for 7
Set value to 255 for DCD timeout. This disables DCD timeout

Select 0 to go back to main menu:
Select 1: Central Station menu

Central station menu

1. Central station 1
2. Central station 2
3. Central station 3
4. Central station 4
5. Up/download menu

0. Back to main menu

Make your choice:  Select 1: Central station 1

Central station 1 menu

1. Account code 1 : 1111101
2. Account code 2 : 1111102
3. Account code 3 : 1111103
4. Account code 4 : 1111104
5. Account code 5 : 1111105
6. Account code 6 : 1111106
7. Account code 7 : 1111107
8. Account code 8 : 1111108
9. Network address: 511100

0. Back to Central Station menu

Make your choice:  Select 9
Network address and make sure there are 6 or more digits. They can be any combination.

Select 0 until you are at the main menu
Select 0: Exit MPI programming and follow instructions

Turn PC-programming dip-switch 3 on to exit.
Goodbye.

 Last and crucial, make sure switch 5 on the MPI232 module is set to OFF. This turns off callback mode.