Modem Capture Connectivity for Galaxy Range

The following panel have been integrated to the WebWay signalling solutionGalaxy 16+ a WebWay modem capture module

WebWayOne Guide - 

Galaxy WebWay Guide Galaxy WebWay Guide (871 KB)


Panel Connection

To install the Galaxy for full remote management you will require the Dial Capture Module (DCM). Connect the WebWay Dial Capture Module (DCM) panel interface A and B to the Galaxy connection telephone terminals labelled A and B. 
Connect the WebWay PWR + and - to the terminals AUX+ and AUX- 



Panel Programming (Galaxy 16 Plus)

1. Enter Engineer Menu 56
2. Go to Menu 12 Comms 1
3. Enter Account number <_____> Site ID (Menu 1)
4. Enter telephone number 1 <01666111> (Menu 2)
5. Select Format (Menu 4)
6. Select SIA level 3
7. Ensure Trigger 10 is on (Menu 7)
8.    Ensure Trigger 18 is on (Menu 7)
9.     Select 4 < (black square) Set/Reset >
10.   Select Access  (Menu 10)
11.   Select <Direct>
12.   Go to Menu 13
13.   Select NO OF RINGS to 01
14.   Escape to Engineer mode

Note that as this is using a dialler no modules will be found by the Galaxy.



Panel Programming (Galaxy Digi)

1. Enter Engineer Menu 56
2. Select Internal Telecoms (1) or Ext Telecoms (5) *
3. Select format (Option 1)
4.    Enter SIA (Option 2)
5.     Select  SIA level 3
6. Ensure Trigger 10 is on
7. Ensure Trigger 18 is on 
8. Select Tel No.1 (option 2)
9.      Set phone number 01234 567890
10.   Select Account Number (option 3)
11.   Enter <_____> (site ID)
12.   Go to remote Access (Option 12)
13.    Select Access Period <Anytime>
14.   Select Mode <Direct Access>

* Depending on how you have connected the WebWay SPT

Galaxy Panel – Hints and tips

Use Menu 23 to check which version of firmware the Galaxy panel is running.

Menu 62 - full test engineer menu can be used to put the system into a false state of close. The engineer can then trigger the sensors for intruders and intruder confirms. This saves engineers having to actually close the site properly.

Line fail (ATS Line Fail to the keypad) on Ethernet can be disabled in;  56  >  4  > 7 = line fail. Set network to OFF.

Line fail (ATS Line Fail to the keypad) on telecoms can also be disabled by using;  56  >  5  > 10 = line fail. Set line voltage to disabled.

To force a dot on the IP address settings a # or * will work to place the dot.

Checking  for a G2 panel; go to Menu 56 > If there is  a menu 6 for H/W Priority then you are working on a G2 panel.

500 Series – If above firmware version V6.0 use S1 not S3 to connect to the data bus.

If you are changing the connection type; i.e from an RS485 Ethernet module to a RS232 module, make sure the account number is removed from the old module settings otherwise alarms will not be delivered.

Testing SIA Events – You will need to test real events; i.e, triggering an actual PA. Toggling outputs will not send alarms.

Galaxy panels running version V.14 and below cannot support SIA and are a pins only integration.