WebWayOne Guide -

HKC - Secure Wave 1070 HKC - Secure Wave 1070 (659 KB)

      

Manufacturer Guide -  

HKC Manufacturer Guide HKC Manufacturer Guide (4511 KB)

Click here for Remote Manager and Upload / Download settings 

HKC Alarm Systems 

The following panels have been integrated to the WebWay signalling solution

SecureWave 1070 Firmware versions 1, 2 and 3
SPT firmware V3.45 firmware version 1 and 2
       SPT firmware version V3.50+ Firmware version 3

Integration is by a serial connection. Serial connectivity requires modification of a HKC serial Cable. (Webway One Cable Part No: 055039)

Serial Panel Connection

Modify a HKC supplied cable by removing the RS232 connector to reveal four coloured wires and connect this as follows.

WebWay SPT

HKC SP1

(From Top to Bottom)

-

Pin 1 -Blank

TTL - R

Pin 2 – TTL - R

TTL - T

Pin 3 – TTL- T

RTN

Pin 4 - RTN

The red wire is not required for integration. The Molexconnector attaches to SP 1 on the panel.
       
 
     
  
                                                              SPT  TTL Wiring                                                                                                                               SecureWave SP 1 Port 

.
Connect the WebWay PWR + and - to any relevant Power (+12V/+24V) and Ground (0V) terminals.

       
Panel Programming -Version 1 and 2 Firmware 
       
       
1. Make sure that SP1 on the HKC panel is set up for Remote PC. 
2. <Comms Menu>                       Press Yes 
3. <Comms Opts Menu>              Press Yes 
4. <SP1 Port Options>  Press Yes 
5. Set <Remote Access>             to YES 
6. Next 
7. Set <Secure Access>              to NO 
8. Next 
9. Set <Local Access>                 to YES 
10. Next 
11. Set <Printer Port>                    to NO.
12. Make sure that SP1 baud is set 2400, Data bits 8, Stop bit 1 and NOPARITY. (defaults) 
13. <Comms Menu>          Press Yes 
14. <Com Service Menu>    Press Yes 
15. <Port Settings> Press Yes 
16. <Com Service Menu>              Press Yes 
To change remote user code from default
1. Select Comms Menu
2. Select Remote User Menu
3. Then select remote user code
4. RO1 Remote user will be displayed, set and verify this as 1234 or as required.
5.  Notify WebWayOne of the new code, or set this using menu H on the webway communicator
       
IMPORTANT - Remote User Security Code

For remote management of the panel and for SIA alarm communication the panel must be programmed with a remote user code.
If remote management is not  required,  the WebWay and SecureWave panel still require the remote user code to send SIA alarms. This is default to1234. The WebWay and SecureWave cannot communicate if this number does not match.
If you wish to set the user code to a number other than 1234 you will need to notify webwayone first in order for the panel to communicate or set the code manually. This is done directly on the webway unit via menu H in the in the same manner as  “Auto Take-On” which uses menu D. 
For site roll outs we can pre populate the WebWay SPT with the required code. For more information on this, or  queries on the remote user security code please contact support on, 01635 231514 or  email; support@webwayone.co.uk.
 
IMPORTANT - HKC Log Translation to SIA (Note when testing alarms with ARC)
If any alarm or event generated by the panel is not in any of the standard tables, a default SIA message is generated with details that can be used to help choose and update the event with the correct SIA Code.
Example 1: [#1818|Nda07-07-1/ti23:01:00|YO|A Unknown System Event 5: Aux Fuse felt Panel] 
Example 2: [#1818|Nda07-07-1/ti07:30:00|YO|A Unknown System Event 26: Entry Fault] 
The Second example had the following SIA codes added to the system event table as DF and DR.
       
 
Panel Programming - HKC Panel firmware Version 3

No major panel settings are required for the webway to integrate to the Panel and then communicate SIA alarms.
Enter engineering mode, code is (04567 by default), it may ask this code to be authorized by a user code, which is by default  01234. Default Ireland User code is 1111
       
Please check the "Remote User Code"...
1. Select Engineer Mode
2. Select Comms Menu
3.     Select Remote User Menu
4. Then select remote user code
5. RO1 Remote user will be displayed, set and verify this as 1234 or as required.
6.  Notify WebWayOne of the new code, or set this using menu H on the webway communicator.

      
    
IMPORTANT - Remote User Security Code - version 2/3 firmware

For remote management of the panel and for SIA alarm communication the panel must be programmed with a remote user code.
If remote management is not required, the WebWay and SecureWave panel still require the remote user code to send SIA alarms. This is default to1234. The WebWay and SecureWave cannot communicate if this number does not match.
Note that Panels with firmware versions 2 or 3 do not default this to 1234. This must be set as detailed below.
If you wish to set the user code to a number other than 1234 you will need to notify WebWayOne first in order for the panel to communicate or set the code manually. This is done directly on the WebWay unit via menu H in the in the same manner as “Auto Take-On” which uses menu D. 
For site roll outs we can pre populate the WebWay SPT with the required code. For more information on this, or queries on the remote user security code please contact support on 01635 231514 or email; support@webwayone.co.uk.